Pipe velocity calculator
Velocity in a pipe from flow and internal diameter, in feet per second.
Preliminary. The reference tables behind this calculation are pending a second check against their printed source. Verify against your adopted edition before using a result in a submitted calculation.
- Internal diameter
- 2.067in
- Flow at 20.0 ft/s
- 209.2gpm
- 20.0 ft/s
- advisorynot a code limit
The formula
v = 0.4085 Q / d^2
- v
- velocity in the pipeft/s
- Q
- flow through the pipegpm
- d
- internal diameter, not the nominal sizein
- 0.4085
- the US customary constant
Velocity is advisory, not a code limit
NFPA 13 does not set a maximum velocity for sprinkler piping. The 20 ft/s figure many designers work to is a practical convention: above it the pipe is noisy, the friction loss is a large share of the total, and small errors in length or fitting count move the answer more than they should.
The full app flags a pipe over the threshold in the notes list and says plainly that it is not a code limit, so an advisory is never mistaken for a compliance failure.
Run the whole system, not one pipe. Same solver, pass or fail against your flow test, NFPA 13 report as a PDF.
Questions about this calculation
- Does NFPA 13 limit pipe velocity?
- No. There is no velocity limit for sprinkler piping in NFPA 13. Some authorities having jurisdiction and some insurers impose one; check locally. The threshold in this tool is a designer convention.
- Why does the nominal size not match the diameter used?
- Nominal size names the pipe, it does not measure the bore. A 2 in schedule 40 pipe has an internal diameter of 2.067 in and a 2 in schedule 10 pipe has more. The calculation uses the internal diameter from the pipe schedule you select.
- What does the 20 ft/s flow figure mean?
- It is the flow that would put this pipe exactly at 20 ft/s, so you can see how much headroom the pipe has before upsizing becomes worth considering.
- Does velocity affect the friction loss calculation?
- Not directly. Hazen-Williams works from flow and diameter, not velocity. Velocity is reported because it is the quantity that tells you whether a pipe is working too hard.